Alternative Fire Test Methods For Walls
Alternative test or classification standards for Group Numbers
Table C1 Alternative test or classification standards for Group Numbers | ||
Requirements according to C/VM2 Appendix A using ISO 9705 and ISO 5660 |
Requirements according to NCC Specification C1.10 Clause 4 using AS ISO 9705 | European Classification using EN 13501-1 |
Group Number 1- S | Group Number 1, and a smoke growth rate index not more than 100 |
Class A1, A2 or Class B and Smoke production rating s1 or s2 |
Group Number 1 | Group Number 1 | Class A1, A2 or B |
Group Number 2- S | Group Number 2, and a smoke growth rate index not more than 100 | Class C and Smoke production rating s1 or s2 |
Group Number 2 | Group Number 2 | Class C |
Group Number 3 | Group Number 3 | Class D |
Group Number 4 | Group Number 4 | Class E and F |